Having a power handling capacity exceeding 500 kVA
Electrical transformers with power handling capacity exceeding 500 kVA
HSN 8504 34 00 (electrical transformers exceeding 500 kVA) is covered by a Bureau of Indian Standards Quality Control Order. Conformity to IS 1180 (Part 1) is mandatory under the ISI Mark Scheme with effect from 07 May 2015, by virtue of the Electrical Transformers (Quality Control) Order, 2015. Bureau of Energy Efficiency labelling compliance applies as a separate customs-clearance overlay.
- 1Source only from a Bureau of Indian Standards CM/L-licensed manufacturer holding a current licence against IS 1180 (Part 1) for outdoor type oil-immersed distribution transformers. Verify the supplier's CM/L number, licensed product scope covering the specific kVA rating and voltage class, and licensed manufacturing facility on the BIS online register before placing the purchase order.Electrical Transformers (Quality Control) Order, 2015 · S.O. 1221(E) dated 07-05-2015
- 2Confirm the IS 1180 (Part 1) product scope against the consignment: the standard covers three-phase ratings up to 2500 kVA and single-phase ratings up to 25 kVA (sealed type) at 33 kV. Transformer ratings or configurations outside this scope are not covered by the CM/L and require separate BIS assessment.IS 1180 (Part 1) · Electrical Transformers (Quality Control) Order, 2015 · S.O. 1221(E) dated 07-05-2015
- 3Ensure every transformer bears the ISI mark and the supplier's CM/L number in accordance with Scheme-I of Schedule-II to the BIS (Conformity Assessment) Regulations, 2018. Marking must appear on the transformer nameplate or body, not on packaging alone.Scheme-I of Schedule-II to the BIS (Conformity Assessment) Regulations, 2018 · Electrical Transformers (Quality Control) Order, 2015
- 4Ensure compliance with the Bureau of Energy Efficiency (Appliance Labelling and Compliance) Regulations, 2026 for transformers within the BEE labelling scope. The BEE labelling reference must accompany consignment-level documentation at the time of customs filing.BEE Notification 5506/BEE/S&L/AL/2025-26 dated 26-12-2025
- 5Quote the supplier's BIS CM/L number on the bill of entry, supported by test reports and conformity documentation. Customs verifies the CM/L in real time against the BIS register; an absent, expired, or scope-mismatched licence triggers consignment detention.Electrical Transformers (Quality Control) Order, 2015 · S.O. 1221(E) dated 07-05-2015 · General Note 2 to Import Policy · BIS Act, 2016
The most common error on this tariff line is sourcing against a CM/L that covers a lower kVA band or a different sealing type — for example, a licence valid for non-sealed three-phase transformers up to 200 kVA presented for a sealed unit rated at 1000 kVA. IS 1180 (Part 1) distinguishes sealed from non-sealed type and separately specifies rating bands; customs officers at major ports routinely cross-check the CM/L scope against the transformer nameplate data sheet, and a rating or sealing-type mismatch results in detention of the full consignment pending re-verification.